GUIDE FOR SETTING OF SUPERHEATSuperheat Adjuster of Expansion Valve adjusts the superheat by which the valve begins to open from the fully closed condition, and this superheat is called Static Superheat.S.S.H.: Static SuperheatO.S.H.: Operating Superheat (Superheat necessary for valve and refrigeration system operation)S.H.C.: Superheat Change (Superheat which keeps the valve opening at the optimum balance point for refrigeration systems)S.S.H. =O.S.H. −S.H.C.To change the adjustment, remove the seal cap and turn the adjusting spindle. Turning the spindle clockwise to compress the spring decreases flow and raises superheat and turning the spindle counter clockwise to loosen the spring increases flow and lowers superheat.CHARGE & MOP (MAXIMUM OPERATING PRESSURE)G–Charge:Gas charge used generally on air conditioning gives pressure limiting, but loses control if valve body becomes colder than sensing bulb. A gas charged valve should be installed in a location where the valve body can be warmer than the bulb to prevent condensation of the charge in the powerhead.L–Charge: Liquid charge provides accurate control when valve body becomes colder than sensing bulb; hence a liquid charged valve may be installed in any location regardless of temperature. The charge, however, does not provide maximum operating pressure (pressure limiting) for motor overload protection.C–Charge:CL–ChargeCY–ChargeCross charge and Cross Low Temp. charge used generally on low temperature range application will not lose control even if valve body becomes colder than sensing bulb. A cross charged valve may be installed in any location regardless of temperature. Cross charge (C) for normal refrigeration (higher than −40°C temp. range) and Cross Low Temp. charge (CL and CY) for low temp. refrigeration (CY...−70 to −40°C with R22 for Type ATX valves).S–Charge:SA–ChargeSL–ChargeSaginomiya,s all purpose special charge combines the best properties of gas and liquid charges. The charge provides accurate control even if valve boby becomes colder than sensing bulb and further it provides MOP (pressure limiting) for motor overload protection. S–charged valve may be installed in any location regardless of temperature.ORDERING INFORMATION1) Catalog Number ... On standard products, specify the Catalog No. only.2) Special Specifications ... On special applications, specify the followings:a)Normal Pressure and Maximum Pressureb)Normal Temperature and Minimum Temperaturec)Detailed Applicationd)Refrigerante)Valve Locationf)Capacity (Condensing & Evaporating Temperature)g)Length of Capillary Tubeh)External or Internal Evaporatori)Pressure Drop at Evaporatorj)MOP (Maximum Operating Pressure)k)Two Stage Compressor System or not

元のページ 

10秒後に元のページに移動します

※このページを正しく表示するにはFlashPlayer10.2以上が必要です