英文S2014_ノンブル無し_高
109/128

R410ACatalog No.Port size (mm)Capacity (U.S.R.T.) {kW}R407CTypeModelPressure drop across the valve (MPa) {kgf/cm2}0.005{0.05}0.01{0.1}0.015{0.15}0.02{0.2}0.025{0.25}0.03{0.3}0.035{0.35}0.04{0.4}HPR–1304D〔B〕P136.14{21.6}8.76{30.8}10.7{37.6}12.4{43.5}13.8{48.5}15.7{55.1}16.6{58.3}17.5{61.6}1305D〔B〕P2207DP2215.1{53.1}21.4{75.1}26.3{92.4}30.4{107}33.8{119}37.0{130}40.1{141}42.9{151}Catalog No.Port size (mm)Capacity (U.S.R.T.) {kW}R410ATypeModelPressure drop across the valve (MPa) {kgf/cm2}0.005{0.05}0.01{0.1}0.015{0.15}0.02{0.2}0.025{0.25}0.03{0.3}0.035{0.35}0.04{0.4}HPR–1304D〔B〕V136.57{23.1}9.36{32.9}11.4{40.2}13.2{46.4}14.7{51.8}16.8{58.9}17.7{62.3}18.7{65.8}1305D〔B〕VR407CAPPLICATION EXAMPLE•Condensation pressure regulating valve type HPRThis product can control the condensing pressure corresponding to the change in the outside temperature, and prevents the condensing pressure decrease in the control in the winter, also steady throughout the year control is possible. This product properly maintains the inlet pressure of the expansion valve and prevents the decrease in the refrigeration capacity.Suitable for use in refrigeration systems with hot gas defrosting and in extremely cold region.DIMENSIONSCondensing Pressure higher than the set value (summer) C→RCondensing Pressure lower than the set value (winter) B→RUnit: mm※φ68(φ92)※R410A:φ7180(120)96(135)92(95)117(160)71(70)80(120)SBCRCondensation pressureregulating valve(Type HPR)Air-cooled type condenserExpansion ValveCompressorEvaporatorAccumulator SolenoidValvesType HPR–1304 to 1305D(Type HPR–2207D)

元のページ 

10秒後に元のページに移動します

※このページを正しく表示するにはFlashPlayer10.2以上が必要です